Purpose of The fire protection system is to detect and suppress fire. When that system is impaired, a trained person physically patrolling the affected area assumes that detection and notification role until the system is restored to service. Fire watch is required under NFPA 1, Chapter 18 and IFC §901.7 whenever a fire protection system — sprinkler, fire alarm, suppression, or detection — is out of service for more than 4 hours in a 24-hour period in an occupied building.

Fire watch is is dispatched in response to a specific impairment condition. When fire watch is required and what it involves — by trigger event.

ActivityFrequencyCode reference
Sprinkler system impairment (any portion out of service)Immediately if >4 hours in 24-hour period while occupiedNFPA 1 §18.2 / IFC §901.7
Fire alarm system impairment (system or zone out of service)Immediately if >4 hours in 24-hour period while occupiedNFPA 1 §18.2 / IFC §901.7
Construction site — before permanent fire alarm operationalDuring all occupied work hours without a functioning systemIFC §3312 / NFPA 241 §9.2
During hot work operations in unprotected areasDuring all hot work; 30-minute post-work patrolNFPA 51B §8.3
AHJ-ordered fire watch (code violation or emergency)Per AHJ order — typically until system is restored or violation correctedIFC §901.7
Patrol frequency during fire watchMinimum every 30 minutes (NFPA 1 §18.6); AHJ may require more frequentNFPA 1 §18.6
Documentation — fire watch log entriesEvery patrol, with time, location, and observationsNFPA 1 §18.6.2

Please call us if you are in need of fire watch. Please call (832) 643-8826